2.5 Derusting and Primer Painting
2.5.1 When parts and steels need derusting,the blasting derusting,shot-blasting derusting,manual derusting and power tool derusting may be adopted.The steel surface after treatment shall be free from welding slag,overlap,spatter,dust,oil stain,water or burrs.After derusting and before painting primer,the surface of parts and steels shall meet the requirements of the current relevant standards of the Nation or design.
2.5.2 When adopting blasting and shot-blasting derusting on the surface of parts and steels,measures shall be taken to control environmental pollutions.The relative humidity of the construction environment shall not be larger than 85%,and the surface of parts and steels shall be free from dew.
2.5.3 When conducting blasting derusting,the compressed air used shall be free from visible oil,water and dirt.
2.5.4 The derusting grade of the surface of parts and steels shall meet the design requirements,and it shall be in accordance with those specified in Table 2.5.4 when there is no requirement of design.
Table 2.5.4 Derusting grade of surface of parts and steels

Note:The derusting grade is detailed in"Rust Grades and Preparation Grades of Steel Surfaces Before Application of Paints and Related Products"(GB 8923).
2.5.5 When painting primer on parts and steels,the ambient temperature and relative humidity shall meet the requirements stated in the technical documents of coating products.Where no requirement is stated in the technical documents of products,the ambient temperature should be 5℃~38℃,and the relative humidity shall not be larger than 85%.When painting,the surface of parts and steels shall be free from dew;within 4h after painting,the surface shall be protected against rain.
2.5.6 The surface of parts and steels shall be free from mistaken coating or lack of coating.The coating shall be even without such obvious defects as wrinkle,sagging,lifting,pinhole,re-rust and bubble.
2.5.7 The milled end face of parts shall be protected by painting varnish after milling.
2.5.8 Before painting primer,the mark shall be transferred;protective measures shall be taken for the weld joint before qualified inspection and for the surface of parts within 50mm at both sides of field joint.The following position shall not be painted with primer:
1 High-strength bolted connection friction surface.
2 Contact surface of column base plate and base.
3 Internal surface of totally enclosed parts.
4 Machining surface required by machinery installation.
5 Position that is not to be painted according to the design.
- DL/T 5526-2017 換流站噪聲控制設計規程
- GB 50222-2017 建筑內部裝修設計防火規范
- 電磁式流量傳感器測量方法及理論
- GB 50469-2016 橡膠工廠環境保護設計規范
- DL/T 5001-2014 火力發電廠工程測量技術規程
- GB/T51154-2015海底光纜工程設計規范(英文版)
- DL/T 5156.1-2015 電力工程勘測制圖標準 第1部分:測量
- GB/T 50459-2017 油氣輸送管道跨越工程設計標準
- 海上架空輸電線路設計技術規程
- GB 51335-2018 聲屏障結構技術標準
- 工控技術應用數學(修訂版)
- GB 50588-2017 水泥工廠余熱發電設計標準
- GB/T 50451-2017 煤礦井下排水泵站及排水管路設計規范
- GB/T 51242-2017 同步數字體系(SDH)光纖傳輸系統工程設計規范
- GB/T 51126-2015 波分復用(WDM)光纖傳輸系統工程驗收規范(英文版)