4 Site Selection and General Arrangement
4.0.1 Power plants and substations shall be built in farorable areas,and shall be away from unfavorable areas;if impossible,effective seismic measures shall be taken.Hazardous areas shall in no case be selected.
4.0.2 Power plants should not be built in an area with a seismic precautionary intensity of 9 degree.When this is unavoidable,important electrical installations shall be located at hard(hard soil or rock)sites.
4.0.3 The railways and roadways of power plants or access roads of substations shall not be built in hazardous areas where collapse,widespread landslide,debris flow,ground fracture or dislocation is likely to occur in the event of earthquake.
4.0.4 Major production buildings(structures)and equipment of electrical installations shall be arranged in areas where the geology and topography are favorable to seismic protection,and shall be away from dangerous areas.
4.0.5 When electrical installations are arranged in the upper or lower platform of a retaining wall or side slope with a height of more than 8m,the distance between the electrical installations and the retaining wall or side slope shall be increased appropriately in view of importance of the electrical installations.
4.0.6 The fuel oil warehouses,acid and alkali warehouses,and liquid ammonia DeNox agent preparation and storage workshops of power plants should be arranged in a relatively low area on sides of the plant area.The tanks containing fuel oil,acid and alkali,or liquid ammonia shall be provided with protective cofferdam around.
4.0.7 The underground pipes and trenches inside power plants should be arranged in a simplified and distributed manner,and should not be arranged in parallel beneath roads.For power plants in areas with a seismic precautionary intensity of 7 to 9 degree,they shall not be arranged beneath main roads.Marks of underground pipes and trenches shall be made on the ground.
4.0.8 The pipes,trenches,and trestles outside power plants should not be arranged in areas where collapse,widespread landslide,debris flow,ground fracture or dislocation is likely to occur in the event of earthquake and should be away from caves and under-consolidated fill soil areas.
4.0.9 Densely populated buildings in power plants,such as the main power house,office building,laboratory building,and canteen,shall be provided with a safety passage roads respectively at the entrance and exit,and with a shelter for evacuation nearby.
4.0.10 The distance between road edges and buildings(structures)in power plants shall be determined such that the fire fighting access will not be blocked by fallouts during an earthquake.
4.0.11 The basic benchmarks of power plants and substations shall not be arranged in unfavorable areas.
- 電動汽車工程手冊(第六卷):智能網聯
- GB50169-2006電氣裝置安裝工程接地裝置施工及驗收規范(英文版)
- 滌綸工廠設計標準
- GB/T 51266-2017 機械工廠年時基數設計標準
- GB 51214-2017 煤炭工業露天礦邊坡工程監測規范
- SH/T3143-2012石油化工往復壓縮機工程技術規范(英文版)
- 鐵路罐車清洗設施設計標準
- 電氣工程師手冊(第4版)
- 鉆探、井探、槽探操作規程
- GB/T 50619-2010(英文版)火力發電廠海水淡化工程設計規范
- GB50742-2012煉鋼機械設備安裝規范(英文版)
- GB 51236-2017 民用機場航站樓設計防火規范
- GB 51304-2018 小型水電站施工安全標準
- GB/T 50466-2018 煤炭工業供暖通風與空氣調節設計標準
- GB 50633-2010(英文版)核電廠工程測量技術規范