3.2 Number of Power Cable Cores
3.2.1 Where the neutral of power sporce of 1kV or below is solidly grounded,the number of cable cores for the three-phase circuit shall be determined in accordance with the following requirements:
1 Where the protective wire is grounded by connecting with the exposed conductive parts of energized equipment,the following requirements shall be met:
1)If the protective wire and the neutral line share the same conductor,four-core cables shall be used.
2)If the protective wire is independent of the neutral line,five-core cables should be used;however,four-core cables together with an additional protective conductor may be used provided that the requirements of Article 5.1.16 of this code are met.
2 Where the earth of exposed conductive parts of energized equipment is independent of that of the power supply system,four-core cables shall be used.
3.2.2 Where the neutral of power supplies of 1kV or below is solidly grounded,the number of cable cores for single-phase circuits shall be selected in accordance with the following requirements:
1 Where the protective wire is grounded by connecting with the exposed conductive parts of energized equipment,the following requirements shall be met:
1)If the protective wire and the neutral line share the same conductor,two-core cables shall be used.
2)If the protective wire is independent of the neutral line,three-core cables should be used;however,two-core cables together with an additional protective conductor may be used provided that the requirements of Article 5.1.16 of this code are met.
2 Where the earth of exposed conductive parts of energized equipment is independent of that of the power supply system,two-core cables shall be used.
3.2.3 The number of cable cores for 3-35kV three-phase power supply circuits shall be selected according to the following requirements:
1 For circuits with a large working current or cables laid underwater,three single-core cables may be used for each circuit.
2 In other cases,three-core cables of ordinary belted type shall be used,or alternatively,three single-core cables in stranded configuration may be used.
3.2.4 For 110kV three-phase power supply circuits,three single-core cables may be used for each circuit,except for cables laid underwater in lakes or seas and with small cable cross sections,in which case three single-core cables may be used.
For three-phase power supply circuits of 110kV or above,three single-core cables shall be used for each circuit.
3.2.5 For HV AC single-phase power supply circuits such as that for electric railways,two-core cables or two single-core cables shall be used for each circuit.
3.2.6 The number of cable cores for DC power supply circuits shall be selected according to the following requirements:
1 For LV DC power supply circuits,two-core cables should be used,and single-core cables may be used as an alternative.
2 For HV DC transmission systems,single-core should be used,and coaxial two-core cables may be used when laid underwater in lakes and seas.
- GB/T 50381-2018 城市軌道交通自動售檢票系統工程質量驗收標準
- 城市地下空間規劃標準
- GB 51227-2017 立井鉆井法施工及驗收規范
- YD/T 5131-2005 移動通信工程鋼塔桅結構設計規范(英文版)
- GB/T 51257-2017 液化天然氣低溫管道設計規范
- SH3011-2011石油化工工藝裝置布置設計規范(英文版)
- GB 51258-2017 玻璃纖維工廠設計標準
- GB 51237-2017 火工品試驗室工程技術規范
- GB 50426-2016 印染工廠設計規范
- 鄭州軌道交通機電設備運營需求標準
- DL/T 5505-2015 電力應急通信設計技術規程
- GB/T 50398-2018 無縫鋼管工程設計標準
- DL/T5161.11-2002電氣裝置安裝工程質量檢驗及評定規程第11部分:電梯電氣裝置施工質量檢驗(英文版)
- 棉紡織工廠設計標準
- GB 50421-2018 有色金屬礦山排土場設計標準